| Model / Specification | EDR-150-24 | |
| OUTPUT | DC Voltage | 24V | 
| Rated Current | 6.5A / 230VAC 5.2A / 115VAC | |
| Current Range | 0 ~ 6.5A / 230VAC 0 ~ 5.2A / 115VAC | |
| Rated Power | 156W / 230VAC 125W / 115VAC | |
| Ripple & Noise | 150mVp-p | |
| (Max) Note 2 | ||
| Voltage ADJ. Range | 24 ~ 28V | |
| Voltage Tolerance Note 3 | ± 1.0% | |
| Line Regulation | ± 0.5% | |
| Load Regulation | ± 1.0% | |
| Setup, Rise Time | 1500ms, 60ms/230VAC | |
| 3000ms, 60ms/115VAC at full load | ||
| Hold up Time (Typ.) | 16ms/230VAC 10ms/115VAC at full load | |
| INPUT | Voltage Range | 90~264VAC 127~370VDC | 
| (DC input operation possible by connecting AC/L(+),AC/N(-) | ||
| Frequency Range | 47-63Hz | |
| Efficiency (Typ.) | 87.00% | |
| AC Current (Typ.) | 2.6A/115VAC 1.7A/230VAC | |
| Inrush Current (Typ.) | 20A/115VAC 35A/230VAC | |
| Leakage Current | <1mA/240VAC | |
| PROTECTION | Overload | 105~130% rated output power | 
| Protection type : Constant current limiting, | ||
| recovers automatically after fault condition is removed / 230VAC | ||
| Over Voltage | 29 ~ 33V | |
| Protection type: Shut down o/p voltage, re-power on to recover | ||
| Over Temperature | Shut down o/p voltage, re-power on to recover | |
| ENVIREMENT | Working Temperature | `-20℃~+60℃ (Refer to Output “Derating Curve”) | 
| Working Humidity | 20%~95% RH non-condensing | |
| Storage Temperature | `-40℃~+85℃, 10~95% RH | |
| and Humidity | ||
| Temp. Coefficient | ±0.03%/°C(0~50°C) | |
| Vibration | Component:10~500Hz, 2G 10min/1cycle, 60min. | |
| Each along X,Y,Z axes; Mounting; Compliance to IEC60068-2-6 | ||
| SAFETY & EMC | Safety Standards | U508, TUV EN60950-1 approved;(meet EN60204-1) | 
| (Note 4) | Withstand Voltage | I/P-O/P;3KVAC I/P-FG;2KVAC I/P-FG;0.5KVAC | 
| Isolation Resistance | I/P-O/P,I/P-FG, O/P-FG;>100M Ohms/500VDC/25℃/70%RH | |
| EMC Emission | Compliance to EN55022 (CISPR22) Class A, | |
| EN61000-3-2, Class A (≤80% Load), EN61000-3-3 | ||
| EMC Immunity | Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, | |
| EN61000-6-2 (EN50082-2), heavy industry level, criteria A | ||
| OTHERS | MTBF | 472.5K hrs min. MIL-HDBK-217F (25°C ) | 
| Dimension | 40*125.2*113.5mm (W*H*D) | |
| Packing | 0.6Kg; 20pcs/13Kg/1.16CUFT | |
NDR150-24 Single Output 24V 150W Din Rail
Winston NDR150-24 Single Output 24V 150W Din Rail Switching Power Supply
- Universal AC Input/Full range
- Protection: short-circuit/ overload/ over voltage/Over temperature
- Cooling by free air convection
- Can be (industrial control equipment) listed
- EN61000-6-2(EN50082-2) industrial immunity level
- 100% full load burn-in test
- Low cost
						