Model | DR-60-5 | DR-60-12 | DR-60-24 | |
output |
DC voltage | 5V | 12V | 24V |
Voltage tolerance | ±2% | ±1% | ±1% | |
Rated current | 6.5A | 4.5A | 2.5A | |
Current range | 0~6.5A | 0~3.5A | 0~2.5A | |
Rated power | 32.5W | 54W | 60W | |
Ripple&noise | 100mvp-p | 100mvp-p | 150mvp-p | |
DCvoltage ADJ.range | -9%~+10% | ±10% | ±10% | |
input |
Voltage range | 90~264VAC,127~373VDC | ||
frequency | 47~63HZ | |||
AC current | 1.2A/110VAC,0.65A/220VAC | |||
efficiency | 76% | 82% | 84% | |
Inrush current | Cold start current 25A/115VAC,50A/230VAC | |||
Leakage current | < 1mA/240VAC | |||
protection |
Over load | Rated output power105%~150% start over load protection | ||
protection type:hiccup mode,auto-recovery after fault condition is removed | ||||
over voltage | 6.8~8.2V | 15.6~17.8V | 30.6~33.2V | |
protection type:cut off output voltage,diode clamp | ||||
environment | Working temp,humidity | -20℃~+60℃,20%~90%RH | ||
Storagetemp,humidity | -40℃~+85℃,10%~95%RH non-condensing | |||
Withstand vibration | 10~500HZ,2G 10min/1cycle,period for 60 minutes,each axes | |||
safety | Withstand voltage | I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC | ||
Isolated resistance | I/P-O/P,I/P-FG,O/P-FG:100M ohms/500VDC | |||
Fitstandard | Safety standard | Fit UL1012 | ||
EMC standard | EN55022,CLASSA | |||
others | Dimension | 78*93*56mm (L*W*H) | ||
Weight/packing | 0.3kg/48pcs/15.4kg/0.03m³/1.07CUFT | |||
note | 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. |
DR-60 Din rail type switching power supply
หมวดหมู่: Din rail power supply(DR and MDR)
ป้ายกำกับ: Switching Power Supply. เพาเวอร์ซัพพลาย, ตัวแปลงไฟฟ้า
รายละเอียดเพิ่มเติม
ข้อมูลเพิ่มเติม
BRANDS |
---|