Model Specification | LP-300W-24 | LP-300W-48 | |
Output | DC Output Voltage | 24 V | 48 V |
Output Voltage tolerance | ± 1% | ± 1% | |
Rated Output Current | 12.5A | 6.25A | |
Output Current Range | 0-12.5A | 0-6.25A | |
DC Output Power | 300 W | 300 W | |
Tripple and Noise | 240mVp-p | 300mVp-p | |
Adjustable Range for DC Voltage | 20.5-26.5V | 44.5-51V | |
Input | AC Input Voltage Range | 85-132VAC/176-264VAC selected by swith or 248-373VDC 47~63Hz; | |
AC input current | 3A/115VAC 1.5A/230VAC | ||
Efficiency | 83% | 85% | |
AC Inrush Current | Cold-Start Current: 15A/115V, 30A/230V | ||
Leakage Current | <2mA/240VAC | ||
Protection charateristic | Overload Protection | 110%-150% | |
Protection mode: cut off output and reset automatically | |||
Over Voltage Protection | 27-30V | 51-54V | |
Protection mode: cut off output and reset automatically | |||
Environment | Work Temperature Humidity | -10°C~+50°C , 20%~90%RH | |
Storage Temperature Humidity | `-20°C~+85°C, 10%~95%RH | ||
Shock resistance | 10~500Hz, 2G 10min,/1cycle,duration:60min each shaft | ||
Safety | Voltage withstand capacity | Input-output:2KVAC Input-earth:1.5KVAC Output-earth:0.5KVAC | |
Insulation resistance | Input-output, Input-earth ,Output-earth:100M Ohms/500VDC | ||
Executive Stantand | Safety Standards | CE | |
EMC Standards | Design refer to FCC part 15J Conduction Class B | ||
Others | Weight | 0.65KGS | |
Package | 24pcs/ctn 38*30*28 | ||
size | 100*60*110(L*W*H) | ||
Notes | 1. All parameters except special situtation, are meaured under 230VAC voltage input and rated load at 25°C. 2. The ripple and noise voltage are measured in condition capacitance of 0.1μ and 47μ are applied to ends of 12inch twisted-pair of 20MHZ bandwidth oscilloscope. 3.The tolerance is the sum of setting voltage error , voltage and current regulation factor. |
DC LP-300 300W 24V power supply unit
รายละเอียดเพิ่มเติม
ข้อมูลเพิ่มเติม
BRANDS |
---|